Pitt-Char XP provides up to 2 hours protection against jet fire impingement.
Pitt-Char Coatings have been fire tested at more than 12 fire testing facilities around the world. Our products have received approvals and certificates from Underwriters' Laboratories Inc. (USA and Canada), Det Norske Veritas (Norway), Lloyd's Registry of Shipping (UK), GASAFE (France), and from several customers based on their own in-house fire testing. Testing has covered a range of heat fluxes including jet fire impingement testing on various steel section geometries and sizes. A sampling of fire test results are listed in the following table. For additional test information, including actual explosion testing up to 1.8 bar overpressures, consult your local Pitt-Char XP Coating Technical Sales Representative.
PRODUCT FIRE TEST RESULTS
|
TEST DESIGN |
TEST METHOD |
FIRE RATING |
|
Structural Steel - Range of Hp/A Values for I Sections and RH Sections |
NordTest Method NT Fire 021 |
1 to 4 hours Hp/A from 25 to 300 Failure Temperatures 200°C to 700°C |
|
Underdecks H60 H120 |
IMO RES using exposure model described in ISO 834 |
11.0 mm (0.43") 15.0 mm (0.59")
|
|
Bulkheads H60 H120 HO-400°C
A-60 |
IMO RES using exposure model described in ISO 834
IMO RES A 0.517 (13) |
10.0 mm (0.39") 14.0 mm (0.55") 7.0 mm (0.28")
8.0 mm (0.31")
|
|
Surface Flammability |
ASTM E-84 |
Flame Spread=15 Smoke Development=70-110 |
|
Column Test UL Design No. X-623 |
UL 263 "Fire Tests of Building Construction and Materials" |
Fire Ratings from 1 to 3 hours Covering Steel Sizes: W/D: .84 to 3.55 Hp/A: 160 to 38 |
|
Beam Test UL Design No. N-612 |
UL 263 "Fire Tests of building Construction and Materials" |
Restrained Beam Rating - 4 hrs. Unrestrained Beam Rating - 3 hrs. Covering Steel Sizes: W/D: .68 to 1.75 Hp/A: 197 to 77 |
|
Column Test UL Design No. XR-612 |
UL 1709 "Fire Tests of Structural Steel Protected for Resistance to Rapid Temperature Rise Fires" |
1 hr.: 0.28"(7.1 mm) 1 1/2 hr.: 0.40"(10.2 mm) 2 hr.: 0.52"(13.2 mm) 2 1/2 hr.: 0.63"(16.0 mm) 3 hr.: 0.75"(19.1 mm) |
|
Jet Fire Test |
OTI 95-634 "Jet Fire Resistance Test of Passive Fire Protection Materials" |
Protection up to 2 hrs. |
|
LPG/LNG Storage Tanks |
US - DOT France - GASAFE |
Protection up to 4 hrs. | |
|
|
|
|
|
|